Trinidad
Water Treatment Plant
 Chlorine System

Click on Picture To Enlarge.

 


Poor PIPING practices, such as lack of hangers and use of schedule 40 Fittings make this system HAZARDOUS !

Poor PIPING practices, such as lack of hangers and use of schedule 40 Fittings make this system HAZARDOUS !

New Bottle Racks w/ Straps meet the State Requirements

Chains DON"T!

Rotameter Looked Glued
This NIPPLE could be shorter,
the BUSHING sent bottoms out!


Had to Chase the threads on the
Regulator for fitting  >>>>

Damage Caused by Liquid Chlorine


Normal Corrosion for all Capital units using Monel screws for Cl2

Same Liquid & Corrosion found on
ALL NXT-3000's used for Cl2

Liquid Cl2 damage might have been prevented with addition of New Manifold!

Liquid Cl2 damage might have been prevented with addition of New Manifold!

Rust is from Steel manifold. May need to clean the manifold every couple of years.